PVC Flat Cable with Earth Conductor - Pektas Cable
FLAT AND CIRCULAR CABLES

PVC Flat Cable with Earth Conductor

Used as surface wiring where there is little mechanical damage risk, or in conduit.
Max. operating temperature
70 °C
Max. short circuit temperature
160 °C
AC test voltage
2kV
Min. bending radius
6 x D
Rated voltage Uo/U
300/500 V
Flame propagation test on single cable
EN 60332-1
Sensitivity
Lead free

Construction

  • 1- Solid or stranded copper (Class 1 or Class 2)
  • 2- Polyvinyl chloride
  • 3- Polyvinyl chloride

Applications

Used as surface wiring where there is little mechanical damage risk, or in conduit.

Technical Data - 624-Y (300/500 V) / Cu/PVC/PVC

Nominal Cross Section mm² Overall Diameter mm (Lower Limit / Upper Limit) Net Weight kg/km Conductor DC Resistance at (20°C) max. ohm/km (Core / Earth) Current Carrying Capacity in Air (A)
1x1re 3.9x5.0 / 4.8x6 41 18.1/18.1 13
1x1.5+1re 4.4x5.4 / 5.3x6.6 48 12.1/18.1 16
1x1.5+1rm 4.5x5.5 / 5.4x6.7 49 12.1/18.1 16
2x1+1re 3.9x7.2 / 4.8x8.7 67 18.1/18.1 13
2x1.5+1re 4.4x8.1 / 5.3x9.7 83 12.1/18.1 16
2x1.5+1rm 4.5x8.3 / 5.4x10.0 84 12.1/18.1 16
2x2.5+1.5re 5.1x9.6 / 6.2x11.7 120 7.41/12.1 21
2x2.5+1.5rm 5.2x9.8 / 6.3x11.9 121 7.41/12.1 21
2x4+1.5rm 5.7x10.8 / 6.9x13.1 172 4.61/12.1 27
2x6+2.5rm 6.4x12.4 / 7.8x15.0 235 3.08/7.41 34
2x10+4rm 7.9x15.6 / 9.5x18.9 373 1.83/4.61 45
2x16+6rm 8.9x18.1 / 10.8x21.9 529 1.15/3.08 57
3x1+1re 3.9x9.4 / 4.8x11.4 91 18.1/18.1 13
3x1.5+1re 4.4x10.7 / 5.3x12.9 117 12.1/18.1 16
3x2.5+1.5re 5.1x12.6 / 6.2x15.3 172 7.41/12.1 21
3x4+1.5rm 5.9x14.8 / 7.1x17.9 243 4.61/12.1 27
3x6+2.5rm 6.4x16.8 / 7.8x20.2 315 3.08/7.41 34
3x10+4rm 7.9x21.3 / 9.5x25.7 516 1.83/4.61 45
3x16+6rm 8.9x24.6 / 10.8x29.7 735 1.15/3.08 57