PVC Double Insulated Wire 6181 Y - Pektas Cable
FLEXIBLE CABLES

PVC Double Insulated Wire 6181 Y

Installation in walls, on boards and in channels or embedded in plaster.
Max. operating temperature
70 °C
Max. short circuit temperature
160 °C
AC test voltage
2kV
Min. bending radius
s ≤ 25 mm²
Rated voltage Uo/U
300/500 V
Flame propagation test on single cable
EN 60332-1
Sensitivity
Lead free

Construction

  • 1- Solid or stranded copper (Class 1 or Class 2)
  • 2- Polyvinyl chloride
  • 3- Polyvinyl chloride

Applications

Installation in walls, on boards and in channels or embedded in plaster.

Technical Data - 6181 Y / Cu/PVC/PVC

Nominal Cross Section mm² Overall Diameter mm Net Weight kg/km Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in Conduit (A)
1 3.9 26 18.1 13.5
1.5 4.2 33 12.1 17.5
2.5 4.9 49 7.41 24
4 6.5 69 4.61 32
6 7.5 89 3.08 41
10 9.1 139 1.83 57
16 11 207 1.15 76
25 13.5 312 0.727 101
35 13.8 410 0.524 125
50 15.6 557 0.387 151
70 18.2 810 0.272 192
95 20.1 1060 0.193 232
120 21.8 1381 0.153 269
150 21.8 1599 0.124 300
185 23.8 1977 0.0991 341
240 27.2 2608 0.0754 400
300 32.5 3055 0.0601 458