PP Insulated Multi-Core Halogen Free Cable - Pektas Cable
FLAT AND CIRCULAR CABLES

PP Insulated, Halogen Free, Flame Retardant, Multi-Core Cables (NHMH)

Refineries, mines, hotels, schools, tunnels, high constructions, hospitals, power plats, data processing centers, populated business centers where there is a risk of fire.
Max. operating temperature
70 °C
Max. short circuit temperature
160 °C
AC test voltage
2kV
Min. bending radius
12 x D
Rated voltage Uo/U
300/500 V
Flame retardant test of bunched cables
EN 60332-3-24 Cat. C
Low smoke
EN 61034
Halogen free
EN 50525-1 - EN 50267

Construction

  • 1- Solid or stranded copper (Class 1 or Class 2)
  • 2- Polypropylene
  • 3- Halogen free flame retardant
  • 4- Halogen free flame retardant

Applications

Refineries, mines, hotels, schools, tunnels, high constructions, hospitals, power plats, data processing centers, populated business centers where there is a risk of fire.

Technical Data - NHMH (300/500 V) / Cu/PP/HFFR/HFFR

Nominal Cross Section mm² Overall Diameter mm Net Weight kg/km Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in Air (A)
2x1.5 7.9 96 12.1 22
2x2.5 8.7 126 7.41 30
2x4 10.0 178 4.61 40
2x6 11.0 231 3.08 51
2x10 13.8 376 1.83 70
2x16 16.4 545 1.15 98
3x1.5 8.3 115 12.1 22
3x2.5 9.2 154 7.41 30
3x4 10.6 222 4.61 40
3x6 12.0 302 3.08 51
3x10 14.6 477 1.83 70
3x16 17.6 709 1.15 98.5
4x1.5 8.9 138 12.1 18.5
4x2.5 9.9 187 7.41 25
4x4 11.9 286 4.61 34
4x6 13.5 390 3.08 43
4x10 15.8 594 1.83 60
4x16 19.4 897 1.15 80
5x1.5 9.6 164 12.1 18.5
5x2.5 10.7 224 7.41 25
5x4 13.2 355 4.61 34
5x6 14.6 470 3.08 43
5x10 17.2 723 1.83 60
5x16 21.5 1111 1.15 80