AER-ABC ALPEK Aluminium Cable - Pektas Cable
ALUMINIUM CABLES

Aerial Bunched Cables (AER-ABC / ALPEK)

Aerial cables used power distribution in populated areas.
Min. bending radius
12 x D
Max. short circuit temperature
PE: 160 °C, XLPE: 250 °C
AC test voltage
3.5 kV
Max. operating temperature
PE: 70 °C, XLPE: 90 °C
Rated voltage Uo/U
0.6/1 kV
Flame propagation test on single cable
EN 60332-1

Construction

  • 1- Stranded aluminium (Class 2)
  • 2- PE or XLPE
  • 3- Alloy aluminium

Applications

Aerial cables used power distribution in populated areas.

Technical Data - AER-ABC / ALPEK (0,6/1 kV) / AL/XLPE (PE)

Nominal Cross Section mm² Diameter of Messenger mm Diameter of Conductor mm Conductor DC Resistance at (20°C) max. ohm/km Resistance max. ohm/km (20°C) Net Weight kg/km
1x16+25 5.9 4.5 1.91 1.38 140
1x25+35 6.9 6.2 1.20 0.986 200
1x35+50 8.1 7.1 0.868 0.72 280
1x16+1x16+25 5.9 4.5 1.91 1.38 210
3x16+25 5.9 4.5 1.91 1.38 280
3x25+35 6.9 6.3 1.20 0.986 400
3x35+50 8.1 7.2 0.868 0.72 560
3x50+70 9.7 8.1 0.641 0.493 730
3x70+95 11.4 9.8 0.443 0.363 1030
3x120+95 11 12.6 0.253 0.363 1150
3x16+1x16+25 5.9 4.5 1.91 1.38 350
3x25+1x16+35 6.9 6.3 1.20/1.91 0.986 480
3x35+1x16+50 8.1 7.2 0.868/1.91 0.72 630
3x50+1x16+70 9.7 7.1 0.641/1.91 0.493 800
3x70+1x16+95 11.4 9.8 0.443/1.91 0.363 1100
4x16+25 5.9 4.5 1.91 1.38 350
4x25+35 6.9 6.1 1.20 0.986 510